RHT Temperature + Humidity Tx. User Manual ABUS TECHNOLOGIES INC.
ABUS TECHNOLOGIES INC. 10 RHT The transmitter requires to be powered during configuration. The ATxConfig provides powering; however th
ABUS TECHNOLOGIES INC. 11 RHT b. Upper Value: sets the value of the input signal that will correspond to the 20 mA output. When the lower limit i
ABUS TECHNOLOGIES INC. 12 RHT 9. SAFETY PRECAUTIONS 1. The unit should be powered for 15 minutes before use. 2. Use in ambient temperature of
ABUS TECHNOLOGIES INC. 2 RHT WARNING This manual should be passed on to the end user. The contents of this manual are subject to change wi
ABUS TECHNOLOGIES INC. 3 RHT CATALOGUE Contents Page No. 1. Introduction 4 2. Presentation Technical Parameters 4 4 3. Dimensions
ABUS TECHNOLOGIES INC. 4 RHT 1. INTRODUCTION The Relative Humidity and Temperature Transmitters RHT-WM and RHT-DM are microprocessor-b
ABUS TECHNOLOGIES INC. 5 RHT IMPORTANT NOTE: The transmitter sensor may be damaged or lose calibration if it is exposed to aggress
ABUS TECHNOLOGIES INC. 6 RHT 3. DIMENSIONS The RHT-DM (Duct Mount) model transmitter should be installed with a flange. This flange is first s
ABUS TECHNOLOGIES INC. 7 RHT The model RHT/WM (Wall Mount) was designed to be mounted directly onto a wall. With the cover off, the user ca
ABUS TECHNOLOGIES INC. 8 RHT 5. CONNECTIONS The transmitter can be ordered as 4-20 mA current output or 0 to 10 Vdc voltage outp
ABUS TECHNOLOGIES INC. 9 RHT 6. INSTALLATION Recommendation Conductors of small electrical signals must be distant from activation